Gold Member Since 2016
Audited Supplier
Wenzhou Kangda Complete Electric Equipment Co., Ltd.

Circuit Breaker, Load Switch, Vacuum Circuit Breaker manufacturer / supplier in China, offering Vsp5 -12 Outdoor Boundary Vacuum Load Switch /Circuit Breaker Series, Zbw Combined Transformer Substation, XL-21 Power Switchgear Distribution Cabinet and so on.

(/ )

Supplier Homepage Product Other Power Supply & Distribution Vsp5 -12 Outdoor Boundary Vacuum Load Switch /Circuit Breaker Series

Vsp5 -12 Outdoor Boundary Vacuum Load Switch /Circuit Breaker Series

FOB Price: Get Latest Price
Min. Order: 1 Piece
Transport Package: Wooden Carton
Payment Terms: L/C, T/T

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: VSP5
  • Origin: Zhejiang, China
Product Description
Product Description
Apply to rated voltage 12KV. Rated frequency 50Hz outdoor AC distribution equipment, use for opening. Closing load current and closing short circuit current. Applicable to substations and industrial and mining enterprises and city, rural network for protection and control purposes, and city, rural network automatic distribution net and frequent operation place.

Applicable to operation of control switch of overhead line distribution systems, there are several types, VPS-12-type boundaries vacuum load switch with no oil, institutional simple. Reliable, no maintenance and other advantages, has been widely used. The product with the FDR-based fault detector or RTU remote terminal unit equipment combine to form a very simple structure, distribution automation system that allows the automatic overhead lines fault location and fault segment of the automatic quarantine. In order to update our existing distribution switchgear, so free of oil and automation features of the distribution equipment for the transformation.

 
ItemUnitsTechnical Parameters
rated voltagekV12
rated currentA630
rated frequencyHz50
rated short time withstand current, timekA20, 4S
rated short-circuit closing current (peak)kA50
operate voltageVAC220(80%-110%)
1min power frequency voltagesEarthkV50(GB standard 42)
Inter-phase50(GB standard 42)
Fracture50(GB standard 48)
Lightning impulse withstand voltageEarthkV95(GB standard 75)
Inter-phase95(GB standard 75)
Fracture110(GB standard 84)
insulation resistanceEarth2000
Inter-phase2000
Fracture2000
per phase lead circuit resistanceµ Ω≤ 500
rated current disconnection lifeTimes10000
mechanical lifeTimes30000
weightkg185
Contact closing bounce durationms≤ 5
Three phase closing and opening non-synchronismms≤ 2
closing timems120-180
opening timems500-900
contact travelmm8-9
contact over travelmm2.5-4
isolation fracture distancemm25-30
isolation fracture over-distancemm7-14
SF6 year leakage < 1%
SF6 gas water contentsPPm< 2
reference standards IEC265-1
 
 
 
Send your message to this supplier