Customization: | Available |
---|---|
Type: | Power Source Arrester |
Structure: | Zinc Oxide Arrester |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
H.V. Surge Arresters are used to protect transformers and other equipments in station and distribution systems against the damage by atmospheric (especially lightning effects) and operational conditions.Metal oxides surge arresters without gaps are designed to prevent probable damages in the case of typical surges in energy systems while it has no negative effect on energy systems in normal operation voltage. This special feature of gapless arresters originating from non-linear characteristics of metal-oxide varistors between voltage and current scales. The non-linear feature is much higher compared to SiC surge arresters.
Arrester
type
|
Rated voltage
Ur (kV
|
Max. continues
operating voltage
|
Residual Voltage (kV) |
|||
as per IEC
|
as per ANSI/IEEE
|
1/10 μs Steep current impuse
|
1/10 μs Steep current impuse
|
30/60μs Switching current impulse
|
||
Uc (kV)
|
MCOV (kV)
|
|||||
YH5W-3/9
|
3
|
2.4
|
2.55
|
11.3
|
9
|
8.9
|
YH5W-6/18
|
6
|
4.8
|
5.1
|
20.5
|
18
|
16
|
YH5W-9/27
|
9
|
7.2
|
7.65
|
31
|
27
|
24
|
YH5W-10/30
|
10
|
8.0
|
9.3
|
34.1
|
30
|
26.6
|
YH5W-11/33
|
11
|
8.8
|
9.35
|
38
|
33
|
29
|
YH5W-12/36
|
12
|
9.6
|
10.2
|
41.5
|
36
|
30.6
|
YH5W-15/45
|
15
|
12.0
|
12.7
|
52
|
45
|
38.3
|
YH5W-18/54
|
18
|
14.4
|
15.3
|
62
|
54
|
46
|
YH5W-21/63
|
21
|
16.8
|
17
|
72.5
|
63
|
53.5
|
YH5W-24/72
|
24
|
19.2
|
19.5
|
82.5
|
72
|
61.2
|
YH5W-27/81
|
27
|
21.6
|
22
|
93.2
|
81
|
69
|
YH5W-30/90
|
30
|
24.0
|
24.4
|
104
|
90
|
80
|
YH5W-33/99
|
33
|
26.4
|
28.0
|
113.8
|
99
|
84.2
|
YH5W-36/108
|
36
|
28.8
|
29.0
|
124.2
|
108
|
91.8
|