Still deciding? Get samples of $ !
Request Sample
|
| Customization: | Available |
|---|---|
| Breaking Capacity: | High Voltage Circuit Breakers |
| Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Item | Unit | Parameter |
| Voltage, current parameters | ||
| Rated voltage | kV | 40.5 |
| Rated short time power frequency withstand voltage (Imin) | kV | 95 |
| Rated lightning impulse withstand voltage (peak) | kV | 185 |
| Rated current | A | 1250, 1600, 2000 |
| Rated short-circuit breaking current | kA | 25, 31.5 |
| Rated operating sequence | O-0.3s-CO-180s-CO | |
| Rated short-circuit current breaking times | times | 12 |
| Rated short-circuit closing current (peak) | kA | 63.80 |
| Rated peak withstand current | kA | 63.80 |
| Rated short-time withstand current | kA | 25, 31.5 |
| Rated short-circuit current duration | S | 4 |
| Average opening velocity | ms | 1.5±0.2 |
| Average closing speed | ms | 0.7±0.2 |
| Contact closing bounce time | ms | <5 |
| Three-phase close (open) synchronization error | ms | <2 |
| Closing time | ms | <150 |
| Opening time | ms | <60 |
| Mechanical life | times | 10000 |
| Rated operational voltage and auxiliary circuits rated voltage | V | DC220, AC220 |
| DC resistance of circle every phase (not including transformer) | μΩ | <100 |
| Dynamic, static contact allowed to wear thickness | mm | 3 |
| Weight | kg | 800 |