Customization: | Available |
---|---|
Application: | Power, Electronic, Instrument |
Phase: | Three |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The transformer rely on air convection for cooling. With the increasing of urban power load, the crowded residentialand high-rise buildings, underground structures, there is an urgent need in transformer with these advantages: furtherload center, preventing fire or explosion and superior environmental performance,and dry-type transformer meet theserequirements.
The transformer is of high mechanical strength, ant-short circuit ability ,better moisture resistance and can be run at100% humidity without preheating treatment before operation, intermitent operation without moisture protection. Thereare advantages :small size, light weight, no cracking, no moire surface, partial discharge low,high insulation level, gooolightning shock resistant performance,free maintenance, strong heat dissipation capabilty, running 150% rated load inthe forced air cooling conditions , flame retardant, explosion-proof, no polution, and directly installed in the load center.Rated capacity(KVA) | Voltage Combination and tap range | connection of transformer winding | No-load loss (w) |
Load loss (W) | No-load current (%) | Short circuit impedance (%) | ||
High voltage(KV) | High voltage taps range (%) | Low voltage(KV) | ||||||
30 50 80 100 125 160 200 250 315 400 500 630 630 800 1000 1250 1600 2000 2500 |
6 6.6 6.6 10 10.5 11 |
±5% ±2x2.5% |
0.4 |
Dyn11 |
130 190 260 280 330 380 435 505 615 685 810 940 910 1065 1240 1460 1715 2135 2520 |
710 1000 1380 1570 1850 2130 2530 2760 3470 3990 4880 5880 5960 6960 8130 9690 11730 14450 17170 |
2.6 2.2 2.2 2 1.8 1.8 1.6 1.6 1.4 1.4 1.4 1.2 1.2 1.2 1.1 1.1 1.1 1.0 1.0 |
4 4 4 4 4 4 4 4 4 4 4 4 6 6 6 6 6 6 6 |